2 Parameters
2.2 List of parameters
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
p0970
TB30 reset parameters / TB30 par reset
TB30
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Board 30 (TB30).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0161 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
1:
100:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
p0970
TM54F reset parameters / TM54F par reset
TM54F_MA
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 54F (TM54F).
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
1:
5:
6:
100:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
For p0970 = 5 the following applies:
The password for Safety Integrated must be set.
When Safety Integrated is enabled, this can result in error messages, which then require an acceptance test to be
performed.
Then save the parameters and carry out a POWER ON.
298
Inactive
Start a parameter reset
Start a BICO interconnection reset
Inactive
Start a parameter reset
Starts a safety parameter reset
Start reset non-safety/safety parameters
Start a BICO interconnection reset
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0