Siemens G130 List Manual page 777

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p7788
Power unit sign-of-life monitoring tolerance window / PU SoL monit tol
VECTOR_G, B_INF
Can be changed: U, T
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
1
Description:
Setting of the tolerance window for the sign of life monitoring for communication to the power unit.
Dependency:
Refer to: A30853
Note:
An active window is generated by means of DRIVE-CLiQ telegrams.
If more than one sign-of-life error appears in the window, then A30853 is output.
The lower the value in p7788, the greater the monitoring tolerance.
p7789
Power unit sign-of-life monitoring fault threshold / PU SoL monit F_thr
VECTOR_G, B_INF
Can be changed: U, T
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the number of consecutive sign-of-life errors that are tolerated for communication to the power unit.
Dependency:
Refer to: F30008
Note:
F30008 is output in the case of a fault.
The higher the value in the parameter, the higher the monitoring tolerance.
p7790[0...15]
Component trace signal / Comp trace sig
VECTOR_G, B_INF
Can be changed: U, T
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the individual signals for the component trace.
For p7790[0...15] = 0, the component trace is deactivated.
For index 0 ... 7:
The signals are set in p7790[0...7], whose characteristic is to be recorded over time.
If "No signal" is set for a trace channel, then the recording duration of the other time characteristics is increased.
For index 8 ... 15:
The signals are set in p7790[8...15], whose instantaneous value is to be recorded.
Value:
0:
1:
2:
3:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
No signal
Pulse frequency
Phase current U
Phase current V
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
9
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
[0] 2
[1] 3
[2] 4
[3] 7
[4] 8
[5] 9
[6] 5
[7] 0
[8] 6
[9] 1
[10...15] 0