Siemens G130 List Manual page 781

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r7827
Firmware update progress display / FW update progress
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
- [%]
Description:
Displays the progress when updating the firmware of the DRIVE-CLiQ components.
p7828[0...1]
Firmware download component number / FW downl comp_no
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0
Description:
Sets the component number for the required DRIVE-CLiQ component.
Index 0:
Component number of the DRIVE-CLiQ component for which a firmware download is to be made.
Index 1:
Component number of the DRIVE-CLiQ component for which the reference firmware version, saved in r7825 on the
memory card/device memory, is to be displayed.
Index:
[0] = Firmware download
[1] = Reference firmware version
Dependency:
Refer to: p0121, p0141, p0151, p7829
Note:
For p7828[0] = 399, the firmware for all of the existing components is downloaded.
The firmware download is started with p7829 = 1.
p7829
Activate firmware download / FW download act
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-1
Description:
Activating the firmware download for the DRIVE-CLiQ components specified in p7828.
1: Activate download.
-1: activate the download and carry out a reset.
0: Download successfully completed.
> 1: Fault code
011: DRIVE-CLiQ component has detected a checksum error.
015: The selected DRIVE-CLiQ components did not accept the contents of the firmware file.
018: Firmware version is too old and is not accepted by the component.
019: Firmware version is not suitable for the hardware release of the component.
101: After several communication attempts, no response from the DRIVE-CLiQ component.
140: Firmware file for the DRIVE-CLiQ component not available on the memory card/device memory.
143: Component has not changed to the mode for firmware download. It was not possible to delete the existing
firmware.
144: When checking the firmware that was downloaded (checksum), the component detected a fault. It is possible
that the file on the memory card/device memory is defective.
145: Checking the loaded firmware (checksum) was not completed by the component in the appropriate time.
156: Component with the specified component number is not available.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
399
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
781

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150