Summary of Contents for Siemens SINAMICS G130

  • Page 3 ___________________ Safety information ___________________ General ___________________ SINAMICS Mechanical installation ___________________ Electrical installation SINAMICS G130 Line reactors ___________________ Technical specifications Operating Instructions Firmware version V5.1 11/2017 A5E00331462A...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Safety information ........................... 5 General safety instructions ....................... 5 General ..............................11 Mechanical installation .......................... 15 Electrical installation..........................19 Technical specifications ........................21 Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 6 Table of contents Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 7: Safety Information

    Safety information General safety instructions WARNING Electric shock and danger to life due to other energy sources Touching live components can result in death or serious injury. • Only work on electrical equipment if you are appropriately qualified. • Always observe the country-specific safety rules for all work. Generally, the following steps apply when establishing safety: 1.
  • Page 8 Safety information 1.1 General safety instructions WARNING Electric shock due to equipment damage Improper handling may cause damage to equipment. For damaged devices, hazardous voltages can be present at the enclosure or at exposed components; if touched, this can result in death or severe injury. •...
  • Page 9 • If you come closer than around 2 m to such components, switch off any radio devices or mobile phones. • Use the "SIEMENS Industry Online Support App" only on equipment that has already been switched off. WARNING Motor fire in the event of insulation overload There is a greater load on the motor insulation as result of a ground fault in an IT system.
  • Page 10 Safety information 1.1 General safety instructions WARNING Fire due to inadequate ventilation clearances Inadequate ventilation clearances can cause overheating of components with subsequent fire and smoke. This can cause severe injury or even death. This can also result in increased downtime and reduced service lives for devices/systems. •...
  • Page 11 Safety information 1.1 General safety instructions Note Important safety instructions for Safety Integrated functions If you want to use Safety Integrated functions, you must observe the safety instructions in the Safety Integrated manuals. Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 12 Safety information 1.1 General safety instructions Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 13: General

    General Description Line reactors limit low-frequency line-side harmonics to permissible values. WARNING Non-observance of the fundamental safety instructions and residual risks The non-observance of the fundamental safety instructions and residual risks stated in Chapter 1 can result in accidents with severe injuries or death. •...
  • Page 14 General Note Length of connection cables The connection cables between line reactor and Line Module, as well as between line reactor and line filter, must be kept as short as possible (max. 5 m). You must use shielded connection cables, whose cable shields are attached at both ends. Shielding can only be omitted if the following conditions are met: •...
  • Page 15 General Power Module Unit rating of the Power Module Suitable line reactor Line voltage 3-phase 660 – 690 VAC 6SL3310-1GH28-5AA3 85 kW 6SL3000-0CH31-1AA0 6SL3310-1GH31-0AA3 90 kW 6SL3000-0CH31-1AA0 6SL3310-1GH31-2AA3 110 kW 6SL3000-0CH31-6AA0 6SL3310-1GH31-5AA3 132 kW 6SL3000-0CH31-6AA0 6SL3310-1GH31-8AA3 160 kW 6SL3000-0CH32-2AA0 6SL3310-1GH32-2AA3 200 kW 6SL3000-0CH32-2AA0 6SL3310-1GH32-6AA3...
  • Page 16 General Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 17: Mechanical Installation

    Mechanical installation Dimension drawing Figure 3-1 Dimension drawing of line reactor Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 18 Mechanical installation Table 3- 1 Dimensions of line reactor, 380 V – 480 V 3 AC (all values in mm) 6SL3000- 0CE32-3AA0 0CE35-1AA0 0CE38-7AA0 0CE41-0AA0 0CE32-8AA0 0CE36-3AA0 0CE33-3AA0 0CE37-7AA0 12.5 212.5 211.5 211.5 84.5 Lengths n1 and n2 correspond to the drill hole spacing Table 3- 2 Dimensions of line reactor, 500 V –...
  • Page 19 Mechanical installation Table 3- 3 Dimensions of line reactor, 660 V – 690 V 3 AC (all values in mm) 6SL3000- 0CH31-1AA0 0CH34-8AA0 0CH38-4AA0 0CH31-6AA0 0CH36-0AA0 0CH32-2AA0 0CH32-7AA0 0CH33-4AA0 12.5 232.5 84.5 56.5 Lengths n1 and n2 correspond to the drill hole spacing Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 20 Mechanical installation Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 21: Electrical Installation

    Electrical installation Connection When connecting the line filter and line reactor, you must take into account the following conditions to ensure that they function correctly: ● Use shielded control cables. The shield must be connected at both ends. ● With analog control cables, connecting the shield at both ends can result in coupled-in noise.
  • Page 22 Electrical installation Line reactors Operating Instructions, 11/2017, A5E00331462A...
  • Page 23: Technical Specifications

    Technical specifications General technical data Table 5- 1 General technical data Line frequency 47 … 63 Hz Product standard EN 61800-5-1 Ambient conditions Storage Transport Operation Ambient temperature -25 ... +70 °C -25 ... +70 °C 0 ... +50 °C Relative air humidity (con- 5 ...
  • Page 24 Technical specifications Detailed technical data Table 5- 2 Technical data for line reactors 3 AC 380 V ... 480 V, part 1 Article number 6SL3000- 0CE32-3AA0 0CE32-8AA0 0CE33-3AA0 0CE35-1AA0 Suitable for Power Module 6SL3310- 1GE32-1AA3 1GE32-6AA3 1GE33-1AA3 1GE33-8AA3 Unit rating of the Power Module Rated voltage 3 AC 380 –10% to 3 AC 480 +10% (-15% <...
  • Page 25 Technical specifications Table 5- 4 Technical data for line reactors 3 AC 380 V ... 480 V, part 3 Article number 6SL3000- 0CE41-0AA0 Suitable for Power Module 6SL3310- 1GE41-0AA3 Unit rating of the Power Module Rated voltage 3 AC 380 –10% to 3 AC 480 +10% (-15% < 1 min) 1060 thmax Power loss...
  • Page 26 Technical specifications Table 5- 6 Technical data for line reactors 3 AC 500 V ... 600 V, part 2 Article number 6SL3000- 0CH36-0AA0 0CH38-4AA0 Suitable for Power Module 6SL3310- 1GF35-8AA3 1GF37-4AA3 1GF38-1AA3 Unit rating of the Power Module Rated voltage 3 AC 500 –10% to 3 AC 600 +10% (-15% <...
  • Page 27 Technical specifications Table 5- 8 Technical data for line reactors 3 AC 660 V ... 690 V, part 2 Article number 6SL3000- 0CH33-4AA0 0CH34-8AA0 0CH36-0AA0 0CH38-4AA0 Suitable for Power Module 6SL3310- 1GH33-3AA3 1GH34-1AA3 1GH35-8AA3 1GH37-4AA3 1GH34-7AA3 1GH38-1AA3 Unit rating of the Power Module Rated voltage 3 AC 660 –10% to 3 AC 690 +10% (-15% <...