For bit 05:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards. This bit is only set if know-how protection is
active and p7765.1 is set = 1 and p7765.0 is set = 0.
For bit 06:
When know-how protection is activated, the drive data can be traced using the device trace function. This bit is only
set if know-how protection is active and p7765.2 is set = 1.
For bit 12:
Together with p7755, the bit is used to monitor write protection.
Bit = 1, if p7755 != 0 and write protection is active (p7760.0 = 1).
Bit = 0, if write protection was deactivated. p7755 is set to 0, and when write protection is activated again, bit 12
remains at 0.
r7760
Write protection/know-how protection status / Wr_prot/KHP stat
VECTOR_G, B_INF,
Can be changed: -
TM31, TM120, TM150,
Data type: Unsigned16
TB30, TM54F_MA,
P-Group: -
TM54F_SL, ENC, HUB
Not for motor type: -
Min
-
Description:
Displays the status for the write protection and know-how protection.
Bit field:
Bit
00
01
02
03
04
05
06
12
Dependency:
Refer to: p7761, p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
For bit 00:
Write protection can be activated/deactivated via p7761 on the Control Unit.
For bit 01:
The know-how protection can be activated by entering a password (p7766 ... p7768).
For bit 02:
If it has already been activated, know-how protection can be temporarily deactivated by entering the valid password
in p7766. In this case, bit 1 = 0 and bit 2 = 1 offset.
For bit 03:
Know-how protection cannot be deactivated, as p7766 is not entered in the OEM exception list (only the factory
setting is possible). This bit is only set if know-how protection is active (bit 1 = 1) and p7766 has not been entered in
the OEM exception list.
For bit 04:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards/Control Units. This bit is only set if know-how
protection is active and in p7765.0 is set = 1.
For bit 05:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards. This bit is only set if know-how protection is
active and p7765.1 is set = 1 and p7765.0 is set = 0.
For bit 06:
When know-how protection is activated, the drive data can be traced using the device trace function. This bit is only
set if know-how protection is active and p7765.2 is set = 1.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Write protection active
Know-how protection active
Know-how protection temporarily withdrawn Yes
Know-how protection cannot be deactivated Yes
Extended copy protection is active
Basic copy protection is active
Trace and measuring functions for
diagnostic purposes active
Reserved Siemens
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
771