2 Parameters
2.2 List of parameters
p3209[0...n]
Zero current signal delay time / I_0_sig t_del
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.00 [s]
Description:
Sets the delay time for the zero current signal for the zero current monitoring.
Dependency:
Refer to: p3207, p3208
Note:
The monitoring function is only carried out for separately excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold in p2161 (r2199.0 = 1).
p3233[0...n]
Torque actual value filter time constant / M_act_filt T
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0 [ms]
Description:
Sets the time constant for the PT1 element to smooth the torque actual value.
The smoothed torque actual value is compared with the threshold values and is only used for messages and signals.
p3235
Phase failure signal motor monitoring time / Ph_fail t_monit
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0 [ms]
Description:
Sets the monitoring time for phase failure detection of the motor.
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Monitoring is only effective for blocksize and booksize power units.
For p3235 = 0 the function is deactivated.
For VECTOR, the following applies:
The monitoring is automatically deactivated during a flying restart for a motor that is still rotating.
p3236[0...n]
Speed threshold value 7 / n_thresh val 7
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: REL
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the signal "speed deviation model/external in tolerance" (BO: r2199.7).
Dependency:
Refer to: r1443, r2169, r2199, p3237
600
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.00 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1000000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2000 [ms]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: -
Max
3000.00 [rpm]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.02 [s]
Access level: 3
Func. diagram: 8013
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
320 [ms]
Access level: 3
Func. diagram: 8012
Unit selection: p0505
Expert list: 1
Factory setting
100.00 [rpm]