Siemens G130 List Manual page 1015

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p9906
Topology comparison comparison stage of all components / Topo_cmpr tot comp
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
0
Description:
Sets the type of comparison between the actual topology and target topology.
The comparison is started by setting the required value.
Value:
0:
1:
2:
3:
99:
Note:
The electronic rating plate comprises the following data:
- component type (e.g. "SMC20")
- article number (e.g. "6SL3055-0AA0-5BA0")
- manufacturer (e.g. SIEMENS)
- hardware version (e.g. "A")
- Serial No. (e.g. "T-P30050495")
When comparing the topology, the following data is compared in the target and actual topologies:
p9906 = 0: Component type, Article Number, Hardware version, Manufacturer, Serial No.
p9906 = 1: Component type, Article Number
p9906 = 2: Component type
p9906 = 3: Component class (e.g. Sensor Module or Motor Module)
p9907
Topology comparison comparison stage of the component number /
Topo_cmpr comp_no
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
0
Description:
Enters the number of the component where the setting of how the actual topology should be compared to the target
topology should be changed.
Dependency:
Refer to: p9908
p9908
Topology comparison comparison stage of a component / Topo_cmpr 1 comp
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
0
Description:
Sets the type of comparison of a component in the target topology with the actual topology.
The comparison is started by setting the required value.
Value:
0:
1:
2:
3:
99:
Dependency:
Refer to: p9907
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
High: Compares the complete electronic rating plate
Average: Compares the component type and the article number
Low: Compares the component type
Minimum: Compares the component class
Topology has different comparison stages
High: Compares the complete electronic rating plate
Average: Compares the component type and the article number
Low: Compares the component type
Minimum: Compares the component class
Topology has different comparison stages
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0