2 Parameters
2.2 List of parameters
r0084[0...1]
CO: Flux actual value / Flux act val
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the flux actual value.
Index:
[0] = Unsmoothed
[1] = Smoothed
Note:
The flux actual value (index 1) smoothed with p1585 is only displayed for separately excited synchronous motors. In
the following cases, the unsmoothed flux actual value is also displayed:
- in the range of the current model.
- during the pole position identification.
- for I/f control.
- for a stalled drive.
r0087
CO: Actual power factor / Cos phi act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the actual active power factor.
r0088
CO: DC link voltage setpoint / Vdc setpoint
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [V]
Description:
Displays the setpoint for the DC link voltage.
r0089[0...2]
Actual phase voltage / U_phase act val
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [V]
Description:
Displays the actual phase voltage.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
Note:
The values are determined from the transistor switch-on duration.
70
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: 5_2
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: -
Unit group: 5_3
Scaling: p2001
Max
- [V]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6726, 6730,
6732
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 6714, 6730,
6732, 6799
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: 6719
Unit selection: p0505
Expert list: 1
Factory setting
- [V]
SINAMICS G130/G150