2 Parameters
2.2 List of parameters
p9611
SI PROFIsafe telegram selection (Control Unit) / SI Ps telegram CU
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the PROFIsafe telegram number for the Control Unit.
Value:
0:
30:
31:
900:
901:
902:
998:
Dependency:
Refer to: p9811, p60022
Note:
For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
p9612
SI PROFIsafe failure response (Control Unit) / SI Ps fail CU
VECTOR_G
Can be changed: C2(95)
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the stop response when PROFIsafe communication fails.
Value:
0:
1:
Dependency:
Refer to: p9812
Note:
For the set stop response STOP B, in order that the OFF3 ramp is actually maintained, when just using Safety Basic
functions, the following must be carefully observed:
- the transition time STOP F to STOP A (p9658, p9858) must be set longer or equal to the SS1 delay time (p9652,
p9852).
- if a higher-level control responds to a drive fault by withdrawing the controller enable signals, for faults F01611 and
F30611, the message type must be changed to alarm (p2118, p2119).
p9620[0...7]
BI: SI signal source for STO (SH)/SBC/SS1 (Control Unit) / SI S_srcSTO/SS1 CU
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned32 / Binary
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Sets the signal source for the following functions on the Control Unit:
STO: Safe Torque Off / SH: Safe standstill
SBC: Safe Brake Control
SS1: Safe Stop 1 (time monitored)
Dependency:
Refer to: p9601
966
No PROFIsafe telegram selected
PROFIsafe standard telegram 30, PZD-1/1
PROFIsafe standard telegram 31, PZD-2/2
PROFIsafe SIEMENS telegram 900, PZD-2/2
PROFIsafe SIEMENS telegram 901, PZD-3/5
PROFIsafe SIEMENS telegram 902, PZD-3/6
Compatibility mode (as for firmware version < 4.5)
STOP A
STOP B
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
998
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
998
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2810
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150