p0361[0...n]
Motor magnetizing inductance q axis saturated / Mot L_magn q sat
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, PMSM, REL,
RESM
Min
0.00000 [mH]
Description:
Sets the saturated magnetizing inductance of the separately excited synchronous motor quadrature to the rotor
direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
p0362[0...n]
Motor saturation characteristic flux 1 / Mot saturat.flux 1
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: RESM
Min
10.0 [%]
Description:
The saturation characteristic (flux as mapping of current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 1st value pair of the characteristic.
Induction motors (ASM) and separately excited synchronous motors (SESM):
The saturation characteristic describes the mapping of the magnetizing current onto the motor flux.
The parameter sets the first motor flux as a [%] referred to the rated motor flux.
Permanent magnet synchronous motors (PMSM):
The saturation characteristic describes the mapping of the stator quadrature axis current onto the stator quadrature
axis flux.
The parameter sets the first stator quadrature axis flux as a [%] referred to the product of the unsaturated quadrature
inductance (p0356) and the rated motor current.
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
The following applies for the stator quadrature axis flux values (PMSM):
20 % < p0362 < p0363 < p0364 < p0365
Refer to: p0366
Notice:
For permanent magnet synchronous motors (PMSM):
If the parameters are not set as specified, i.e. not in ascending order and to more than 20 %, the unsaturated
quadrature inductance (p0356) is always used for quadrature axis flux calculation purposes.
Note:
For induction motors, p0362 = 100 % corresponds to the rated motor flux.
For separately excited synchronous motors p0362 = 100% corresponds to an induced terminal voltage with the
magnitude of the rated motor voltage (under no-load conditions at the synchronous speed).
With permanent-magnet synchronous motors, p0362 = 100 % corresponds to the product of the unsaturated
quadrature inductance (p0356) and the rated motor current (p0305).
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: CALC_MOD_EQU
Dyn. index: MDS, p0130
Unit group: 15_1
Scaling: -
Max
10000.00000 [mH]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
800.0 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6727
Unit selection: p0349
Expert list: 1
Factory setting
0.00000 [mH]
Access level: 3
Func. diagram: 6723, 6726
Unit selection: -
Expert list: 1
Factory setting
60.0 [%]