Dependency:
Refer to: F06000, F07802, F07840, F30027
Notice:
The maximum time to precharge the DC link is monitored in the power unit and cannot be changed. The maximum
duration of the precharging depends on the power class and the power unit design.
The monitoring time for the precharging is started after the ON command (BI: p0840 = 0/1 signal). Fault F30027 is
output when the maximum precharging duration is exceeded.
Note:
The factory setting for p0857 depends on the power class and the design of the power unit.
The monitoring time for the ready signal of the power unit includes the time to precharge the DC link and, if relevant,
the de-bounce time of the contactors.
If an excessively low value is entered into p0857, then after enable, this results in the corresponding fault.
p0858[0...n]
BI: Unconditionally close holding brake / Uncond close brake
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "unconditionally close holding brake".
Dependency:
Refer to: p0855
Note:
The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (unconditionally
open holding brake).
For a 1 signal via BI: p0858, the command "unconditionally close the holding brake" is executed and internally a zero
setpoint is entered.
p0860
BI: Line contactor feedback signal / Line contact feedb
VECTOR_G, B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal from the line contactor.
Recommendation:
When the monitoring is activated (BI: p0860 not equal to r0863.1), then to control the line contactor, signal BO:
r0863.1 of its own drive object should be used.
Dependency:
Refer to: p0861, r0863
Refer to: F07300
Notice:
The line contactor monitoring is deactivated if the control signal of the particular drive object is set as the signal
source for the feedback signal of the line contactor (BI: p0860 = r0863.1).
Note:
The state of the line contactor is monitored depending on signal BO: r0863.1.
When the monitoring is activated (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is
closed before it is controlled using r0863.1.
p0861
Line contactor monitoring time / LineContact t_mon
VECTOR_G, B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0 [ms]
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5000 [ms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2501, 2701,
2707
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2634, 8734,
8834, 8934
Unit selection: -
Expert list: 1
Factory setting
863.1
Access level: 2
Func. diagram: 2634, 8734,
8834, 8934
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
281