2 Parameters
2.2 List of parameters
p0205
Power unit application / PU application
VECTOR_G
Can be changed: C2(1, 2)
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Overloading the load duty cycles applies under the prerequisite that before and after the overload, the drive converter
is operated with its base load current - in this case, a load duty cycle of 300 s is used as basis.
For booksize drive units, the following applies:
Only the setting p0205 = 0 can be selected. In this particular case, the base load current has a load duty cycle of 150
% for 60 s and 176 % for 30 s.
For chassis units, the following applies:
The base load current for a low overload condition is based on a load duty cycle 110 % for 60 s and 150 % for 10 s.
The base load current for a high overload condition is based on a load duty cycle 150 % for 60 s and 160 % for 10 s.
Value:
0:
1:
6:
7:
Note:
When the parameter is changed, all of the motor parameters and the control mode are pre-assigned according to the
selected application.
The parameter has no influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
r0206[0...4]
Rated power unit power / PU P_rated
VECTOR_G, B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [kW]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
r0207[0...4]
Rated power unit current / PU PI_rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Arms]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
112
Load duty cycle with high overload
Load duty cycle with low overload
S1 continuous duty (for servo drives)
S6 load duty cycle (for servo drives)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
7
Calculated: -
Dyn. index: -
Unit group: 14_6
Scaling: -
Max
- [kW]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [Arms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6
Access level: 2
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
- [kW]
Access level: 2
Func. diagram: 8021
Unit selection: -
Expert list: 1
Factory setting
- [Arms]