2 Parameters
2.2 List of parameters
p3865[0...7]
BI: Braking Module pre-alarm I*t shutdown / BM I*t shutdown
B_INF (Brk Mod ext)
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the message "pre-alarm I*t shutdown" of the Braking Module.
BI: p3865[0...7] = 1 signal --> no pre-alarm, I*t shutdown
BI: p3865[0...7] = 0 signal --> pre-alarm I*t shutdown (A06901)
Dependency:
Refer to: A06901
Note:
For the Braking Module, this message is output via the following terminal:
- X21.4 for the "Booksize" format
This function is not supported for the "chassis" format.
p3866[0...7]
BI: Braking Module fault / BM fault
B_INF (Brk Mod ext)
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the "Fault" message of the Braking Module.
BI: p3866[0...7] = 1 signal --> No fault
BI: p3866[0...7] = 0 signal --> fault (A06900)
For a 0 signal, an acknowledgment via BO: r3861 is automatically carried out at certain time intervals.
Dependency:
Refer to: A06900
Note:
For the Braking Module, this message is output via the following terminal:
- X21.4 for the "Booksize" format
- X21.5 for the "Chassis" format
p3880
BI: ESM activation signal source / ESM act s s
VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source to activate the essential service mode (ESM) via digital input.
Using this function, when required the motor can be operated for as long as possible (e.g. to extract smoke).
BI: p3880 = 1 signal:
The essential service mode is activated.
BI: p3880 = 0 signal:
The essential service mode is deactivated.
Dependency:
The function can only be activated for SINAMICS G130/G150/S150.
Refer to: p3881, p3882, p3883, p3886, r3887, p3888, r3889
Warning:
When activating the essential service mode (BI: p3880 = 1 signal), the motor immediately runs according to the
selected setpoint source. When the essential service mode is activated, the motor cannot be stopped using the OFF
commands.
Note:
ESM: Essential Service Mode
Permissible signal sources:
- BO: r0722.x (high active)
- BO: r0723.x (low active), x = 0 ... 17, 20, 21
630
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
0