p0120
Number of Power unit Data Sets (PDS) / PDS count
VECTOR_G, B_INF
Can be changed: C1(3)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
1
Description:
Sets the number of Power unit Data Sets (PDS).
The value corresponds to the number of power units connected together for a parallel circuit configuration.
Dependency:
Refer to: p0107, r0107
Note:
This parameter is only significant for drive objects A_INFEED and VECTOR with a parallel circuit configuration.
p0121[0...n]
Power unit component number / PU comp_no
VECTOR_G, B_INF
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
The power unit data set is assigned to a power unit using this parameter.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a power unit.
Dependency:
Refer to: p0107, r0107
Note:
For parallel circuit configurations, the parameter index is assigned to a power unit.
p0124[0...n]
Main component detection using LED / M_comp detect LED
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: Converter
CU_G150_DP
Not for motor type: -
Min
0
Description:
Detection of the main components of the drive object selected via the index.
p0124[0...n]
Power unit detection via LED / PU detection LED
VECTOR_G, B_INF
Can be changed: U, T
Data type: Unsigned8
P-Group: Converter
Not for motor type: -
Min
0
Description:
Detects the power unit assigned to this drive and data set.
Note:
While p0124 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate power unit.
For parallel circuit configurations, the parameter index is assigned to a power unit.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
8
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
199
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0