2 Parameters
2.2 List of parameters
r1568[0...5]
CO: Synchronous reluctance motor flux channel / RESM flux channel
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, SESM,
REL
Min
- [%]
Description:
Display and connector output for signals of the flux channel for a synchronous reluctance motor (RESM).
The values are referred to the rated motor flux of the in-line axis (p0357 * r0331).
Index:
[0] = Setpoint before filter
[1] = Optimum flux characteristic output
[2] = Minimum value at low speed
[3] = Dynamic load-dependent boost
[4] = Field weakening value total
[5] = Field weakening value precontrol
Note:
RESM: reluctance synchronous motor (synchronous reluctance motor)
p1569[0...n]
CI: Supplementary torque 3 / M_suppl 3
VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
-
Description:
Sets the signal source for supplementary torque 3.
Dependency:
Refer to: p3842
Notice:
The signal input is after the torque limit (r1538, r1539). For vector drives, the signals that are entered are only limited
by the current and power limits.
Note:
The signal input is preferably used to enter the friction characteristic. The friction compensation is also effective if the
speed controller output reaches its torque limits, but the current limits have still not been reached (this only applies to
vector drives).
p1570[0...n]
CO: Flux setpoint / Flex setp
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: PMSM, REL
Min
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
The following applies for a synchronous reluctance motor:
Scaling the flux setpoint.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
The following applies for a synchronous reluctance motor:
The scaling allows the flux setpoint to be adapted when operating with load-dependent optimum flux characteristic or
with constant flux setpoint.
416
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: p2003
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.0 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 2
Func. diagram: 7010
Unit selection: -
Expert list: 1
Factory setting
3841[0]
Access level: 3
Func. diagram: 6722
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]