2 Parameters
2.2 List of parameters
p2000
Reference speed reference frequency / n_ref f_ref
ENC
Can be changed: T
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
6.00 [rpm]
Description:
Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
p2000
Reference velocity reference frequency / v_ref f_ref
ENC (Lin_enc)
Can be changed: T
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
0.60 [m/min]
Description:
Sets the reference quantity for velocity and frequency.
All velocities or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: Reference frequency (in Hz) = reference velocity (in (m/min) / 60)
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
p2001
Reference voltage / Reference voltage
VECTOR_G, B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
10 [Vrms]
Description:
Sets the reference quantity for voltages.
All voltages specified as relative value are referred to this reference quantity. This also applies for direct voltage
values (= rms value) like the DC link voltage.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Note:
This reference quantity also applies to direct voltage values. It is not interpreted as rms value, but as DC voltage
value.
Note:
For the automatic calculation (p0340 = 1, p3900 > 0) an appropriate pre-assignment is only made if the parameter is
not inhibited from being overwritten using p0573 = 1.
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
For infeed units, the parameterized device supply voltage (p0210) is pre-assigned as the reference quantity.
Example:
The actual value of the DC link voltage (r0070) is connected to a test socket (e.g. p0771[0]). The actual voltage value
is cyclically converted into a percentage of the reference voltage (p2001) and output according to the parameterized
scaling.
492
Calculated: CALC_MOD_ALL
Dyn. index: -
Unit group: -
Scaling: -
Max
210000.00 [rpm]
Calculated: CALC_MOD_ALL
Dyn. index: -
Unit group: -
Scaling: -
Max
600.00 [m/min]
Calculated: CALC_MOD_ALL
Dyn. index: -
Unit group: -
Scaling: -
Max
100000 [Vrms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3000.00 [rpm]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
120.00 [m/min]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1000 [Vrms]
SINAMICS G130/G150