p9554
SI Motion transition time STOP E to SOS (SBH) (Control Unit) / SI Mtn t E->SOS CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition time from STOP E to "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9354
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SOS: Safe Operating Stop / SBH: Safe operating stop
p9555
SI Motion transition time STOP F to STOP B (Control Unit) / SI Mtn t F->B CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition time from STOP F to STOP B.
Dependency:
Refer to: C01711
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
p9556
SI Motion STOP A delay time (Control Unit) / SI Mtn IL t_del CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the delay time for STOP A after STOP B.
In the case of encoderless motion monitoring functions with safe brake ramp monitoring (p9506 = 1) and the OFF3
ramp enabled at the same time (p9507.3 = 0), the parameter has no effect.
Dependency:
Refer to: p9560
Refer to: C01701
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
p9557
SI Motion STO test time (Control Unit) / SI Mtn IL t_test
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the time after which STO must be active when initiating the test stop.
Dependency:
Refer to: C01798
Note:
A change only becomes effective after a POWER ON.
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
600000.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
600000.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3600000.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000.00 [ms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
0.00 [ms]
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
953