Siemens G130 List Manual page 471

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p1845[0...n]
Actual value correction evaluation factor Lsig / ActVal_cor ev Lsig
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0.00
Description:
Sets the weighting factor for the leakage inductance of the L-R element of the actual value correction.
Dependency:
Refer to: p0391, p0392, p0393
Note:
The load-dependent adaptation of the leakage inductance of the current actual value correction is defined using
p0391 ... p0393.
p1846[0...n]
Actual value correction damping factor / ActV_corr D_factor
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0.00
Description:
Sets the damping factor for the actual value correction.
The factor multiplies the T0/Tsig ratio in the feedback branch of the LR element.
r1848[0...5]
Actual value correction phase currents / ActVal_corr I_ph
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Displays phase correction currents as well as the drive converter phase currents
Index:
[0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
r1849[0...5]
Actual value correction phase voltages / ActVal_corr U_ph
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Displays the phase correction voltages and and the drive converter phase voltages
Index:
[0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.00
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.00
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.00
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-