r2225.0
CO/BO: Technology controller fixed value selection status word / Tec_ctr FixVal ZSW
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: Unsigned16
P-Group: Technology
Not for motor type: -
Min
-
Description:
Display and BICO output for the status word of the fixed value selection of the technology controller.
Bit field:
Bit
00
r2229
Technology controller number actual / Tec_ctrl No. act
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: Unsigned32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Displays the number of the selected fixed setpoint of the technology controller.
Dependency:
Refer to: r2224
p2230[0...n]
Technology controller motorized potentiometer configuration / Tec_ctr mop config
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the configuration for the motorized potentiometer of the technology controller.
Bit field:
Bit
00
02
03
04
Dependency:
Refer to: r2231, p2240
Notice:
The following prerequisites must be fulfilled in order to be able to save the setpoint in a non-volatile fashion:
- Firmware with V2.3 or higher.
- Control Unit 320 (CU320) with hardware version C or higher (module with NVRAM).
Note:
For bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1: The setpoint for the motorized potentiometer is saved and after ON is entered using r2231. In order to save in a
non-volatile fashion, bit 03 should be set to 1.
For bit 02:
0: Without initial rounding-off
1: With initial rounding-off.
The selected ramp-up/down time is correspondingly exceeded. The initial rounding-off is a sensitive way of
specifying small changes (progressive reaction when keys are pressed). The jerk for initial rounding is independent
of the ramp-up time and only depends on the selected maximum value (p2237).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Technology controller fixed value selected
Signal name
Data save active
Initial rounding-off active
Non-volatile data save active for p2230.0 =
1
Ramp-function generator always active
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
Access level: 2
Func. diagram: 7950
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 7954
Unit selection: -
Expert list: 1
Factory setting
0000 0100 bin
0 signal
No
No
No
No
FP
7950,
7951
FP
-
-
-
-
567