Siemens G130 List Manual page 511

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r2054
PROFIBUS status / PB status
CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Status display for the PROFIBUS interface.
Value:
0:
1:
2:
3:
4:
Note:
For r2054 = 3:
In state 3 (the LED flashes green), a cyclic connection has been established to the PROFIBUS master; however, one
of the following prerequisites is missing for cyclic operation:
- no setpoints are being received as the PROFIBUS master is in the STOP condition.
Only for clock-cycle synchronous operation, the following applies:
- the drive is not in synchronism as the global control (GC) has an error.
For r2054 = 4:
In the status 4 (LED green), the cyclic connection to the PROFIBUS master has been established and setpoints are
being received. The clock cycle synchronization is OK, the global control (GC) is error-free.
This state does not provide any statement regarding the quality of the clock cycle synchronous sign-of-life characters
on the drive objects.
r2055[0...2]
PROFIBUS diagnostics standard / PB diag standard
CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Diagnostics display for the PROFIBUS interface.
Index:
[0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
r2057
PROFIBUS address switch diagnostics / PB addr sw diag
CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency:
Refer to: p0918
Notice:
The display is updated after switching on, and not cyclically.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
OFF
No connection (search for baud rate)
Connection OK (baud rate found)
Cyclic connection with master (data exchange)
Cyclic data OK
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
511

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents