Siemens G130 List Manual page 601

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p3237[0...n]
Hysteresis speed 7 / n_hysteresis 7
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the hysteresis speed for the signal "speed deviation model/external" (BO: r2199.7).
Dependency:
Refer to: r2199, p3236
p3238[0...n]
OFF delay n_act_motor model = n_act external / t_del n_a = n_ext
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: REL
Min
0.0 [s]
Description:
Sets the OFF delay for the signal "speed deviation model/external in tolerance" (BO: r2199.7).
The smoothed actual speed of the motor model r2169 is compared with the speed measured externally r1443
(threshold value p3236).
Dependency:
Refer to: p3236, p3237
p3240[0...n]
CI: I2t input value signal source / I2t in_value s_src
VECTOR_G (Ext msg) Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PMSM, REL,
RESM
Min
-
Description:
Sets the signal source for the input value of the freely parameterizable I2t monitoring.
Dependency:
Refer to: p3241, p3242, p3243, r3244
Refer to: A07823, F07824
Notice:
To activate the freely parameterizable I2t monitoring, the following applies:
- the function module "Extended messages/monitoring" must be activated (r0108.17 = 1).
- the maximum duration must be set greater than zero (p3242 > 0).
Note:
Application example:
Excitation current monitoring for the separately excited synchronous motor.
p3241[0...n]
Permissible I2t continuous value / Perm I2t cont val
VECTOR_G (Ext msg) Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: ASM, PMSM, REL,
RESM
Min
10.00 [%]
Description:
Sets the permissible continuous value of the freely parameterizable I2t monitoring.
The integrator value in r3244 decreases if the value received via connector input p3240 is higher than the value set in
p3241.
The integrator value in r3244 increases if the value received via connector input p3240 is less than the value set in
p3241.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: -
Max
200.00 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.0 [s]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.00 [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8012
Unit selection: p0505
Expert list: 1
Factory setting
2.00 [rpm]
Access level: 3
Func. diagram: 8012
Unit selection: -
Expert list: 1
Factory setting
3.0 [s]
Access level: 4
Func. diagram: 8022
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: 8022
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
601