p1254
Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
VECTOR_G (n/M)
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: REL
Min
0
Description:
Activates/deactivates the automatic sensing of the switch-in level for the Vdc_max controller.
Value:
0:
1:
p1255[0...n]
Vdc_min controller time threshold / Vdc_min t_thresh
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
0.000 [s]
Description:
Sets the time threshold for the Vdc_min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized.
Prerequisite: p1256 = 1
Dependency:
Refer to: F07406
Notice:
If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1240 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the event
of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
p1256[0...n]
Vdc_min controller response (kinetic buffering) / Vdc_min response
VECTOR_G (n/M)
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: REL
Min
0
Description:
Sets the response for the Vdc_min controller (kinetic buffering).
Value:
0:
1:
Dependency:
Refer to: F07405, F07406
p1257[0...n]
Vdc_min controller speed threshold / Vdc_min n_thresh
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
0.00 [rpm]
Description:
Sets the speed threshold for the Vdc-min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized .
Kinetic buffering is not started below the speed threshold.
Note:
Exiting the Vdc_min control before reaching motor standstill prevents the regenerative braking current from
increasing significantly at low speeds, and after a pulse inhibit, means that the motor coasts down.
However, the maximum braking torque can be set via the appropriate torque limiting.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Automatic detection inhibited
Automatic detection enabled
Buffer Vdc until undervoltage, n<p1257 -> F07405
Buff. Vdc until undervolt., n<p1257 -> F07405, t>p1255 -> F07406
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: -
Max
210000.00 [rpm]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
50.00 [rpm]