2 Parameters
2.2 List of parameters
Note:
The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
Parameter p4099[0] must never be equal to zero.
p4099[0...2]
TB30 inputs/outputs sampling time / TB30 I/O t_sample
TB30
Can be changed: C1(3)
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the sampling time for the inputs and outputs of Terminal Board 30 (TB30).
Index:
[0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The sampling times can only be set as an integer multiple of the lowest basic sampling time (r0110[0]).
Refer to: p0009, r0110, r0111
Note:
The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
For clock cycle synchronous PROFIBUS operation, the TB30 hardware (e.g. analog/digital converter) is operated
with the PROFIBUS clock cycle (r2064[1]). This clock cycle is also kept after the PROFIBUS connection has been
exited up to the next time that the Control Unit is switched off. In this case, a faster sampling time than the
PROFIBUS clock cycle is not practical in p4099[0...2].
p4100[0...3]
TM120 temperature evaluation, sensor type / TM120 sensor type
TM120
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the sensor type for temperature evaluation via Terminal Module 120 (TM120).
This means that the temperature sensor type is selected and the evaluation is switched in.
Value:
0:
1:
2:
4:
6:
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
Notice:
For p4102[0...7] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100[0...3] = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...7] must be set <= 250 °C.
Note:
The temperature sensors are connected to the following terminals:
X521.2(+) and X521.1(-) = channel 0
X521.4(+) and X521.3(-) = channel 1
X521.6(+) and X521.5(-) = channel 2
X521.8(+) and X521.7(-) = channel 3
666
Evaluation disabled
PTC thermistor
KTY84
Bimetallic NC contact
PT1000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5000.00 [µs]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9099, 9100
Unit selection: -
Expert list: 1
Factory setting
[0] 4000.00 [µs]
[1] 4000.00 [µs]
[2] 4000.00 [µs]
Access level: 1
Func. diagram: 9605, 9606
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150