r0027
CO: Absolute actual current smoothed / I_act abs val smth
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [A]
Description:
Displays the smoothed absolute actual current value.
Dependency:
Refer to: r0068
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
r0028
Modulation depth smoothed / Mod_depth smth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the smoothed actual value of the modulation depth.
Dependency:
Refer to: r0074
Note:
A_INF: Smoothing time constant = 300 ms
SERVO, VECTOR: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
r0029
Current actual value field-generating smoothed / Id_act smooth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Displays the smoothed field-generating actual current.
Dependency:
Refer to: r0076
Note:
SERVO: Smoothing time constant = 100 ms
VECTOR: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
50
Calculated: -
Dyn. index: -
Unit group: 6_4
Scaling: p2002
Max
- [A]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2002
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2002
Max
- [Arms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 8750
Unit selection: p0505
Expert list: 1
Factory setting
- [A]
Access level: 3
Func. diagram: 5730, 6799,
8950
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 5730, 6799
Unit selection: -
Expert list: 1
Factory setting
- [Arms]