p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint. For
the setpoint change there is no rounding-off.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
VECTOR_G
Can be changed: C2(1), U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note:
This time can be exceeded if the DC link voltage reaches its maximum value.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [s]
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1138[0...n]
CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal
VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
Refer to: p1120
Note:
The ramp-up time is set in p1120.
p1139[0...n]
CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency:
Refer to: p1121
Note:
The ramp-down time is set in p1121.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
600.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
30.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
30.000 [s]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 3060, 3070
Unit selection: -
Expert list: 1
Factory setting
3.000 [s]
Access level: 2
Func. diagram: 3070
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: 3070
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 3
Func. diagram: 3060, 3070
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 3060, 3070
Unit selection: -
Expert list: 1
Factory setting
1