2 Parameters
2.2 List of parameters
For passive infeeds (Basic Line Module) the following applies:
- BI: p0840 = 0 signal: OFF1 (precharging contactor/line contactor open)
- BI: p0840 = 0/1 signal: ON (precharging contactor/line contactor close)
r0863.1 of a drive can also be selected as signal source.
Switching on can be delayed with a wait time (p0862).
Switching off can also be delayed with a wait time (p3490).
p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_src 1
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the first signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switching-on inhibited)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- no OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_src 1
B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the first signal source for the command to instantaneously switch off the drive.
This corresponds to command "No coast down/coast down (OFF2)" for drives.
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switching-on inhibited)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- no OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
For binector input p0844 = 0 signal or p0845 = 0 signal, the following applies:
- precharging contactor/line contactor is additionally opened.
276
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2501, 8720,
8820, 8920
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 8720, 8820,
8920
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150