r0267.0...7
BO: Cooling unit status word / RKA ZSW
VECTOR_G
Can be changed: -
(Cool_unit), B_INF
Data type: Unsigned16
(Cool_unit)
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the status word of the cooling unit.
Bit field:
Bit
00
01
02
03
04
05
06
07
Dependency:
Refer to: p0266
p0278
DC link voltage undervoltage threshold reduction / Vdc U_under red
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
-80 [V]
Description:
Sets the absolute value by which the threshold to initiate the undervoltage fault (F30003) is reduced.
Dependency:
Refer to: p0210, r0296
Refer to: F30003
Notice:
When using a Control Supply Module (CSM) for 24 V supply from the DC link, the minimum continuous DC link
voltage may not lie below 430 V. DC link voltages in the range 300 ... 430 V are permissible up to a duration of 1 min.
For chassis power units, this parameter has no significance.
Note:
The resulting shutdown threshold can be read in r0296 and is dependent on the selected rated voltage (p0210) and
the power unit being used.
p0279
DC link voltage offset alarm threshold / Vdc offs A thresh
B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
0 [V]
Description:
Sets the voltage threshold to initiate alarm A06810.
The value represents an offset so that the alarm threshold is obtained from the total of r0296 and p0279.
Dependency:
Refer to: p0210, r0296
Refer to: A06810
Note:
The absolute value of the undervoltage threshold r0296 depends on the selected unit supply voltage (p0210).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
RKA switched on
RKA ready for switching on
RKA no alarm present
RKA no fault present
RKA no leaked fluid
RKA liquid flow OK
RKA conductivity no fault
RKA conductivity no alarm
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
0 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
500 [V]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [V]
Access level: 3
Func. diagram: 8760, 8864,
8964
Unit selection: -
Expert list: 1
Factory setting
0 [V]
FP
-
-
-
-
-
-
9974
9974
125