Siemens G130 List Manual page 497

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p2024[0...2]
Fieldbus interface times / Fieldbus times
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
0 [ms]
Description:
Sets the time values for the fieldbus interface.
For Modbus the following applies:
p2024[0, 1]: Not relevant.
p2024[2]: Telegram pause time (pause time between two telegrams).
Index:
[0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency:
Refer to: p2020, p2030
Note:
For p2024[2] (Modbus):
If the field bus baud rate is changed (p2020), the default time setting is restored.
The default setting corresponds to a time of 3.5 characters (dependent on the baud rate that has been set).
r2029[0...7]
Field bus int error statistics / Field bus error
CU_G130_DP,
Can be changed: -
CU_G150_DP
Data type: Unsigned32
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the receive errors on the field bus interface (USS).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2030
Field bus int protocol selection / Field bus protocol
CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
3
Description:
Sets the communication protocol for the field bus interface.
Value:
3:
6:
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
PROFIBUS
USS (X140)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
[0] 1000 [ms]
[1] 0 [ms]
[2] 0 [ms]
Access level: 3
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3
497

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150