2 Parameters
2.2 List of parameters
r4101[0...3]
TM120 sensor resistance / TM120 R_sensor
TM120
Can be changed: -
Data type: Unsigned16
P-Group: Terminals
Not for motor type: -
Min
- [ohm]
Description:
Displays the actual resistance value of the temperature sensor connected at the Terminal Module.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
Note:
The maximum measurable resistance value is approx. 1720 Ohm.
The temperature sensors are connected to the following terminals:
X521.2(+) and X521.1(-) = channel 0
X521.4(+) and X521.3(-) = channel 1
X521.6(+) and X521.5(-) = channel 2
X521.8(+) and X521.7(-) = channel 3
r4101[0...11]
TM150 sensor resistance / TM150 R_sensor
TM150
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [ohm]
Description:
Displays the actual resistance value of the temperature sensor connected at the Terminal Module.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Note:
The maximum measurable resistance value is approx. 2500 Ohm.
For 1x2 and 2x2 wire evaluation:
The actual sensor resistance is displayed in this parameter(i.e. the wire resistance (p4110) is taken into account).
The temperature sensors are connected to the following terminals:
X531 = channel 0 (for 2x2 wire evaluation, additionally channel 6)
X532 = channel 1 (for 2x2 wire evaluation, additionally channel 7)
X533 = channel 2 (for 2x2 wire evaluation, additionally channel 8)
X534 = channel 3 (for 2x2 wire evaluation, additionally channel 9)
X535 = channel 4 (for 2x2 wire evaluation, additionally channel 10)
X536 = channel 5 (for 2x2 wire evaluation, additionally channel 11)
Details on the wiring are included in the parameter description for p4108.
668
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [ohm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [ohm]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9605, 9606
Unit selection: -
Expert list: 1
Factory setting
- [ohm]
Access level: 3
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
- [ohm]
SINAMICS G130/G150