Note:
For bit 01:
The interpolator is only effective in following cases:
- isochronous PROFIBUS operation with a sign-of-life received from the master (STW2.12 ... STW2.15).
r1197
Fixed speed setpoint number actual / n_set_fixed No act
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Displays the number of the selected fixed speed/velocity setpoint.
Dependency:
Refer to: p1020, p1021, p1022, p1023
Note:
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1198.0...15
CO/BO: Control word setpoint channel / STW setpoint chan
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Display and BICO output for the control word of the setpoint channel.
Bit field:
Bit
00
01
02
03
05
06
11
13
14
15
r1199.0...8
CO/BO: Ramp-function generator status word / RFG ZSW
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Displays the status word for the ramp-function generator (RFG).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Fixed setp bit 0
Fixed setp bit 1
Fixed setp bit 2
Fixed setp bit 3
Inhibit negative direction
Inhibit positive direction
Setpoint inversion
Motorized potentiometer raise
Motorized potentiometer lower
Bypass ramp-function generator
Signal name
Ramp-up active
Ramp-down active
RFG active
Ramp-function generator set
Ramp-function generator held
Ramp-function generator tracking active
Maximum limit active
Ramp-function generator acceleration
positive
Ramp-function generator acceleration
negative
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 3010
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2505
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
Access level: 3
Func. diagram: 3001, 3080
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
FP
3010
3010
3010
3010
3040
3040
3040
3020
3020
3060,
3070
FP
-
-
-
-
-
-
-
-
-
333