2 Parameters
2.2 List of parameters
r0032
CO: Active power actual value smoothed / P_actv_act smth
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [kW]
Description:
Display and connector output for the smoothed actual value of the active power.
Dependency:
Refer to: r0082
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note:
Significance for the drive: Power output at the motor shaft
Significance for the infeed: Line power drawn
For A_INF, B_INF and S_INF the following applies:
The active power is available smoothed (r0032 with 300 ms) and unsmoothed (r0082).
The following applies for SERVO:
The active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed (r0082[0]).
For VECTOR and VECTORMV, the following applies:
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
r0033
Torque utilization smoothed / M_util smooth
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the smoothed torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque in reference to the torque limit, scaled using
p2196.
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
For M_set total (r0079) > 0, the following applies:
- Required torque = M_set total
- Actual torque limit = M_max upper effective (r1538)
For M_set total (r0079) <= 0, the following applies:
- Required torque = - M_set total
- Actual torque limit = - M_max lower effective (r1539)
For the actual torque limit = 0, the following applies: r0033 = 100 %
For the actual torque limit < 0, the following applies: r0033 = 0 %
52
Calculated: -
Dyn. index: -
Unit group: 14_10
Scaling: r2004
Max
- [kW]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 5730, 6799,
8750, 8850, 8950
Unit selection: p0505
Expert list: 1
Factory setting
- [kW]
Access level: 3
Func. diagram: 8012
Unit selection: -
Expert list: 1
Factory setting
- [%]
SINAMICS G130/G150