For bit 06:
Precharging via the Motor Module is activated using this bit. To do this, while precharging, the undervoltage threshold
for the pulse enable is reduced.
Precharging via the Motor Module can only be activated for S120 devices for separately excited synchronous
generators where the DC link voltage control has been preselected (technology controller function module).
p0212
Power unit configuration / PU config
B_INF
Can be changed: C2(2)
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
-
Description:
Sets the power unit configuration.
Bit field:
Bit
00
02
05
Dependency:
For bit 00:
Reduced supply voltages are only possible on booksize power units.
Bit 0 = 1 can only be set if r0192.22 = 1.
Refer to: r0192, p0210
Caution:
For bit 00:
Working with reduced input voltages correspondingly reduces undervoltage detection.
This function may only be used by personnel with expert knowledge!
Note:
For bit 00 = 0:
It is not possible to reduce the supply voltage in p0210 to below 180 V.
For bit 00 = 1:
With this setting the supply voltage in p0210 can be reduced to 70 V.
Bit 0 = 1 can only be set for booksize power units with a rated power of up to 40 kW.
The activation of this function is retentively saved in the unit and for incorrect design of the application can result in
loss of warranty!
For bit 02:
Reserved. It is not permissible to set to 1.
For bit 05 = 1:
The status of the inputs/outputs for the power unit contactors is displayed in r0256.
This only applies to chassis power units with 3 AC line connection and line contactors.
The status display is only effective after parameter save and POWER ON.
p0230
Drive filter type motor side / Drv filt type mot
VECTOR_G
Can be changed: C2(1, 2)
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the type of the filter at the motor side.
Value:
0:
1:
2:
3:
4:
Dependency:
The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Drive unit line supply voltage reduced
Reserved
Contactor display inputs/outputs status
No filter
Motor reactor
dv/dt filter
Sine-wave filter Siemens
Sine-wave filter third-party
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 bin
0 signal
No
No
No
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
FP
-
-
9814
117