2 Parameters
2.2 List of parameters
p1208[0...1]
BI: AR modification infeed / AR modification
VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source to modify the automatic restart (AR).
Interconnections between the automatic restart and infeed:
With the following interconnection in the mode p1210 = 6, the automatic restart can respond to infeed faults:
BI: p1208[0] = r2139.3
With the following interconnection, in the mode p1210 = 4, the automatic restart can respond to line supply failure of
the infeed:
BI: p1208[1] = r0863.2
Index:
[0] = Infeed fault
[1] = Infeed line supply failure
Dependency:
Refer to: r0863, r2139
p1210
Automatic restart mode / AR mode
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
Sets the automatic restart mode (AR).
Value:
0:
1:
4:
6:
14:
16:
Recommendation:
For brief line supply failures, the motor shaft may still be rotating when restarting. The "flying restart" function (p1200)
might need to be activated to restart while the motor shaft is still rotating.
Dependency:
The automatic restart requires an active ON command (e.g., via a digital input). If, for p1210 > 1, there is no active
ON command, then the automatic restart is interrupted.
When using an Operator Panel in the LOCAL mode, then there is no automatic start.
For p1210 = 14, 16, a manual acknowledgment is required for an automatic restart.
Refer to: p0840, p0857, p1267
Refer to: F30003
Danger:
If the automatic restart is activated (p1210 > 1) if there is an ON command (refer to p0840), the drive is switched on
as soon as any fault messages that are present can be acknowledged. This also occurs after the line supply returns
or the Control Unit boots if the DC link voltage is again present or the feedback of the line supply infeed (refer to
p0864) is again available. This automatic switching-on operation can only be interrupted by withdrawing the ON
command.
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1). When faults
are present, therefore, the parameter cannot be changed.
For p1210 > 1, the motor is automatically started.
Note:
For p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledgment,
then these are also automatically acknowledged again. p1211 has no influence on the number of acknowledgment
attempts.
338
Inhibit automatic restart
Acknowledge all faults without restarting
Restart after line supply failure w/o additional start attempts
Restart after fault with additional start attempts
Restart after line supply failure following man. acknowledgment
Restart after fault following manual acknowledgment
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0