if the value 0 is displayed in all indices, then components are not detected via DRIVE-CLiQ.
If a value F hex occurs at a position of the coding (abcd efgh hex), then an overflow has occurred.
p0099[0...5]
Device target topology / Device_target topo
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Topology
CU_G150_DP
Not for motor type: -
Min
0000 hex
Description:
Sets the device target topology in coded form (refer to r0098). The setting is made during commissioning.
Deactivated or non-available components are also counted
Index:
[0] = DRIVE-CLiQ socket X100
[1] = DRIVE-CLiQ socket X101
[2] = DRIVE-CLiQ socket X102
[3] = DRIVE-CLiQ socket X103
[4] = DRIVE-CLiQ socket X104
[5] = DRIVE-CLiQ socket X105
Dependency:
The parameter can only be written into for p0097 = 0.
To perform an automatic device configuration run, an index of the device target topology must be set to the value of
the device actual topology in r0098 for acknowledgment. An index of the device actual topology with a value other
than 0 must be selected.
Refer to: p0097, r0098
Refer to: A01330
Note:
The parameter can only be set to the values 0, the value of the actual device topology, the value of the actual device
target topology and FFFFFFFF hex.
If the value 0 is displayed in all of the indices, then the system has still not been commissioned.
The value FFFFFFFF hex indicates that the topology was not generated by the automatic device configuration but
was commissioned using the commissioning software (e.g. using parameter download).
p0100
IEC/NEMA mot stds / IEC/NEMA mot stds
VECTOR_G
Can be changed: C2(1)
Data type: Integer16
P-Group: Converter
Not for motor type: SESM
Min
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
1:
Dependency:
If p0100 is changed, all of the rated motor parameters are reset. Only then are possible unit changeovers made.
The units of all motor parameters are changed that are involved in the selection of IEC or NEMA (e.g. r0206, p0307,
p0316, r0333, r0334, p0341, p0344, r1493, r1969).
Refer to: r0206, p0210, p0300, p0304, p0305, p0307, p0308, p0309, p0310, p0311, p0314, p0320, p0322, p0323,
p0335, r0336, r0337, p1800
Note:
The parameter can only be changed for vector control (p0107).
The parameter value is not reset when the factory setting is restored (p0010 = 30, p0970).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
IEC motor (50 Hz supply, SI units)
NEMA motor (60 Hz supply, US units)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
FFFF FFFF hex
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0