p2126[0...19]
Change acknowledge mode fault number / Chng ackn F_no
All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2127[0...19]
Change acknowledge mode mode / Chng ackn mode
All objects
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Not for motor type: -
Min
1
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
2:
3:
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
Notice:
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
p2128[0...15]
Faults/alarms trigger selection / F/A trigger sel
All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency:
If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
Refer to: r2129
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Acknowledgment only using POWER ON
Ack IMMEDIATELY after the fault cause has been removed
Acknowledgment only for PULSE INHIBIT
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 8050, 8070
Unit selection: -
Expert list: 1
Factory setting
0
545