2 Parameters
2.2 List of parameters
p0869
Sequence control configuration / Seq_ctrl config
VECTOR_G
Can be changed: T
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the configuration for the sequence control.
Bit field:
Bit
00
Dependency:
Refer to: p0867
Note:
For bit 00:
After withdrawing the OFF1 enable (signal source of p0840), the main contactor is opened after the main contactor
holding time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switching-on inhibited must be acknowledged via the signal source of
p0840 = 0 (OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the
main contactor will open.
p0869
Sequence control configuration / Seq_ctrl config
B_INF
Can be changed: T
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the configuration for the sequence control.
Bit field:
Bit
01
Notice:
For chassis units, the following applies:
Setting p0869.1 = 1 is not permissible, if, using p0860 the internal circuit breaker is monitored (this is not controlled
with r0863.1).
Note:
For bit 01:
For p0869.1 = 1, before starting to charge the DC link (r0899.8 = 1), the system waits for a feedback signal from the
external main contactor (p0860 = 1 signal). The main contactor must be controlled using r0863.1.
Waiting for the contactor feedback signal is especially necessary if the external main contactor has long switching
times, which would lead to the precharging time being exceeded (F06000, F30027).
r0873
CO/BO: Infeed total operation / INF total oper
B_INF
Can be changed: -
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the operational readiness of the infeeds when using Smart Line Module (SLM) and Basic Line Module
(BLM) together (mixed operation).
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be
interconnected to BO: r0863.0 of the other infeed.
Dependency:
Refer to: r0863, p0874
Note:
Mixed operation is not possible with the Active Line Module (ALM)!
284
Signal name
Keep main contactor closed for STO
Signal name
Wait for the feedback signal from the
external main contactor
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
No
Access level: 3
Func. diagram: 8732, 8832,
8932
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
No
Access level: 2
Func. diagram: 8732, 8832
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150
FP
-
FP
-