Siemens G130 List Manual page 277

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p0845[0...n]
BI: No coast-down / coast-down (OFF2) signal source 2 / OFF2 S_src 2
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the second signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switching-on inhibited)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- no OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is effective.
p0845[0...n]
BI: No coast-down / coast-down (OFF2) signal source 2 / OFF2 S_src 2
B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the second signal source for the command to instantaneously switch off the drive.
This corresponds to command "No coast down/coast down (OFF2)" for drives.
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switching-on inhibited)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- no OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is effective.
Note:
For binector input p0844 = 0 signal or p0845 = 0 signal, the following applies:
- precharging contactor/line contactor is additionally opened.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2501, 8720,
8820, 8920
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 8720, 8820,
8920
Unit selection: -
Expert list: 1
Factory setting
1