r7744[0...n]
IGBT power cycling counter valve 5 / IGBT load count 5
VECTOR_G, B_INF
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the status of power cycling counter for valve 5.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
Dependency:
Refer to: p7786
Notice:
After a valve has been replaced, the corresponding power cycling counter must be reset.
Note:
The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 5:
1. Switch off the system and replace valve 5.
2. Switch on the system and acknowledge that valve 5 has been replaced (p7786.5 = 1).
--> the power cycling counter of valve 5 is reset (r7744 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.5 is automatically set to 0.
r7745[0...n]
IGBT power cycling counter valve 6 / IGBT load count 6
VECTOR_G, B_INF
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the status of power cycling counter for valve 6.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
Dependency:
Refer to: p7786
Notice:
After a valve has been replaced, the corresponding power cycling counter must be reset.
Note:
The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 6:
1. Switch off the system and replace valve 6.
2. Switch on the system and acknowledge that valve 6 has been replaced (p7786.6 = 1).
--> the power cycling counter of valve 6 is reset (r7745 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.6 is automatically set to 0.
r7758[0...19]
KHP Control Unit serial number / KHP CU ser_no
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the actual serial number of the Control Unit.
The individual characters of the serial number are displayed in the ASCII code in the indices.
For the commissioning software, the ASCII characters are displayed uncoded.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Notice:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
769