Note:
The interface configuration (p8900 and following) is activated with p8905 = 1.
The parameter is not influenced by setting the factory setting.
p8904
IE DHCP mode / IE DHCP mode
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0
Description:
Sets the DHCP mode for the Industrial Ethernet interface (X127) on the Control Unit.
The actual DHCP mode is displayed in parameter r8914.
Value:
0:
2:
3:
Dependency:
Refer to: p8905, r8914
Note:
The interface configuration (p8900 and following) is activated with p8905.
The parameter is not influenced by setting the factory setting.
p8905
IE Interface configuration / IE IF config
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0
Description:
Setting to activate the interface configuration for the Industrial Ethernet interface (X127) on the Control Unit.
p8905 is automatically set to 0 at the end of an operation.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p8900, p8901, p8902, p8903, p8904
Refer to: A08561
Note:
When a project is downloaded, the interface configuration is only activated if, in the offline project, parameter p8905
is set = 1 or 2.
For p8905 = 1:
The interface configuration (p8900 and following) is activated.
For p8905 = 2:
The interface configuration (p8900 and following) is activated and saved to non-volatile memory.
For p8905 = 3:
The interface configuration is reset to the factory setting at all points.
The factory settings for the interface configuration are loaded on activation (p8905 = 1) or at the next POWER ON.
p8908
Activate FTP / Act FTP
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0
Description:
Activation of the FTP server.
Permits the FTP access to the /INSTALL/SINAMICS directory of the memory card.
Value:
0:
1:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
DHCP off
DHCP on, identification using MAC address
DHCP on, identification via name of station
No function
Activate configuration
Activate and save configuration
Delete configuration
No
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
877