2 Parameters
2.2 List of parameters
Note:
For index 0:
Displays the internal firmware version (e.g. 04402315).
This firmware version is the version of the memory card/device memory and not the CU firmware (r0018), however,
normally they have the same versions.
For index 1:
Displays the external firmware version (e.g. 04040000 -> 4.4).
For automation systems with SINAMICS Integrated this is the runtime version of the automation system.
For index 2:
Displays the internal firmware version of the parameter backup.
With this CU firmware version, the parameter backup was saved, which was used when powering up.
r7850[0...n]
Drive object operational/not operational / DO ready for oper
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-32786
Description:
Displays whether, for an activated drive object, all activated topology components are available or not (or whether
these can be addressed).
0: Drive object not ready for operation
1: Drive object ready for operation
p7852
Number of indices for r7853 / Qty indices r7853
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
1
Description:
Displays the number of indices for r7853[0...n].
This corresponds to the number of DRIVE-CLiQ components that are in the target topology.
Dependency:
Refer to: r7853
Note:
The values are valid if all available Control Units adopt the "Initialization finished" state (r3988 = 800) following power
up.
r7853[0...n]
Component available/not available / Comp present
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
0000 hex
Description:
Displays the component and whether this component is currently present.
High byte: Component number
Low byte: 0/1 (not available/available)
Dependency:
Refer to: p7852
Note:
The values are valid if all available Control Units adopt the "Initialization finished" state (r3988 = 800) following power
up.
788
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
32767
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
200
Calculated: -
Dyn. index: p7852
Unit group: -
Scaling: -
Max
FFFF hex
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents