p1330[0...n]
CI: U/f control independent voltage setpoint / Uf U_set independ.
VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
-
Description:
Sets the signal source for the voltage setpoint for U/f control with an independent voltage setpoint (p1300 = 19).
Dependency:
Selects the U/f control with independent voltage setpoint via p1300 = 19.
Refer to: p1300
p1331[0...n]
Voltage limiting / U_lim
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
50.00 [Vrms]
Description:
Limiting the voltage setpoint.
This means that the output voltage can be reduced with respect to the calculated maximum voltage r0071 and the
start of field weakening.
Note:
The output voltage is only limited if, as a result of p1331, the maximum output voltage (r0071) is fallen below.
p1333[0...n]
U/f control FCC starting frequency / U/f FCC f_start
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.00 [Hz]
Description:
Sets the starting frequency at which FCC (Flux Current Control) is activated.
Dependency:
The correct operating mode must be set (p1300 = 1, 6).
Warning:
An excessively low value can result in instability.
Note:
For p1333 = 0 Hz, the FCC starting frequency is automatically set to 6 % of the rated motor frequency.
p1334[0...n]
U/f control slip compensation starting frequency / Slip comp start
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.00 [Hz]
Description:
Sets the starting frequency of the slip compensation.
Note:
For p1334 = 0, the starting frequency of the slip compensation is automatically set to 6 % of the rated motor
frequency.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: p2001
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: 5_1
Scaling: -
Max
2000.00 [Vrms]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
3000.00 [Hz]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
3000.00 [Hz]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 6300
Unit selection: p0505
Expert list: 1
Factory setting
1000.00 [Vrms]
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.00 [Hz]
Access level: 3
Func. diagram: 6310
Unit selection: -
Expert list: 1
Factory setting
0.00 [Hz]