Drive-Cliq Detailed Diagnostics Configuration / Dq Diag Config; Drive-Cliq Detailed Diagnostics Time Interval / Dq Detail T_Interv; Target Topology Feature Delete All Components / Feature Delete - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

p9938

DRIVE-CLiQ detailed diagnostics configuration / DQ diag config

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Integer16
CU_DC_S
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the configuration for the DRIVE-CLiQ detailed diagnostics (r9943).
Using the detailed diagnostics, it is possible to investigate data transfer errors on an individual connection, selected
using p9942.
Value:
0:
1:
2:
3:
4:
5:
6:
Dependency:
The functions in p9938 can only be set for p9937.0 = 0.
Refer to: r9936, p9937, p9939, p9942
Notice:
If value = 0:
- detailed diagnostics is inactive.
- the error counter is active (r9936).
If value > 0:
- the error counter is inactive (r9936).
- the detailed diagnostics as configured is active (r9943).
p9939

DRIVE-CLiQ detailed diagnostics time interval / DQ detail t_interv

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: FloatingPoint32
CU_DC_S
P-Group: -
Not for motor type: -
Min
1 [s]
Description:
Sets the time interval for recording the error counter in r9943.
Dependency:
Refer to: r9936, p9938, p9942, r9943
p9941

Target topology feature delete all components / Feature delete

CU_DC, CU_DC_R,
Can be changed: C1(1)
CU_DC_R_S,
Data type: Unsigned32
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0
Description:
For p9941 =1, the serial numbers of all components in the target topology are deleted (zero is written).
Through activation and de-activation this enables the actual topology components to be newly assigned to the target
topology components.
Note:
p9941 is automatically set to 0 at the end of the operation.
A warm restart is triggered automatically after p0009 = 0.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Inactive
Sum send and receive errors
Only send errors
Only receive errors
Siemens internal
Siemens internal
Siemens internal
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3600 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0
367

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents