Possible reasons for booting being interrupted:
- power supply interrupted.
- CPU crashed.
- parameterization invalid.
Remedy:
- carry out a POWER ON (power off/on). After switching on, the module reboots from the valid parameterization (if
available).
- restore the valid parameterization.
Examples:
a) Carry out a first commissioning, save, carry out a POWER ON (switch-off/switch-on).
b) Load another valid parameter backup (e.g. from the memory card), save, carry out a POWER ON (switch-
off/switch-on).
Note:
If the fault situation is repeated, then this fault is again output after several interrupted boots.
A01019

Writing to the removable data medium unsuccessful

Message value:
-
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The write access to the removable data medium was unsuccessful.
Remedy:
Remove and check the removable data medium. Then run the data backup again.
A01020

Writing to RAM disk unsuccessful

Message value:
-
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A write access to the internal RAM disk was unsuccessful.
Remedy:
Adapt the file size for the system logbook to the internal RAM disk (p9930).
See also: p9930 (System logbook activation)
F01023

Software timeout (internal)

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An internal software timeout has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
F01030

Sign-of-life failure for master control

Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
For active PC master control, no sign-of-life was received within the monitoring time.
The master control was returned to the active BICO interconnection.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
875