Dependency:
This parameter is preassigned as standard (see note).
After writing information to p8809, p8805 is automatically set to = 1.
Refer to: p8805
Note:
For p8805 = 0 (factory setting) the following applies:
Parameter p8809 contains the information described below.
Re p8809[0...3]:
Contains the value from r9781[0] "SI change tracking checksum functional".
Re p8809[4...7]:
Contains the value from r9782[0] "SI change tracking time stamp checksum functional".
Re p8809[8...53]:
Reserved.
p8811

SINAMICS Link project selection / SINAMICS Link proj

CU_DC (PROFINET
Can be changed: C1(1)
CBE20), CU_DC_R
Data type: Integer16
(PROFINET CBE20),
P-Group: Communications
CU_DC_R_S
Not for motor type: -
(PROFINET CBE20),
CU_DC_S
Min
(PROFINET CBE20)
16
Description:
Project selection for SINAMICS Link.
Value:
16:
64:
Note:
SINAMICS Link requires that the appropriate CBE20 firmware version is selected (p8835 = 3).
The parameter must be set the same for all participants.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p8812[0...1]

SINAMICS Link settings / SINAMICS Link cl c

CU_DC (PROFINET
Can be changed: C1(1)
CBE20), CU_DC_R
Data type: Unsigned16
(PROFINET CBE20),
P-Group: Communications
CU_DC_R_S
Not for motor type: -
(PROFINET CBE20),
CU_DC_S
Min
(PROFINET CBE20)
0
Description:
Sets the clock cycle for SINAMICS Link.
Re index 0:
0 = clock synchronous mode not activated, 1 = clock synchronous mode activated
Re index 1:
Possible values: 500, 1000, 2000 µs
Index:
[0] = Activate isochronous mode
[1] = Bus CC [µs]
Dependency:
Refer to: p8811
Note:
SINAMICS Link requires that the appropriate CBE20 firmware version is selected (p8835 = 3).
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Re index 0:
Is applicable for the synchronization of the application. The SINAMICS Link itself is always synchronous.
Re index 1:
The value must be set the same for all participants.
When newly selecting the project p8811, p8812[1] is set to the factory setting.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
SINAMICS Link project 16 participants
SINAMICS Link project 64 participants
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
64
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2000
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2198
Unit selection: -
Expert list: 1
Factory setting
64
Access level: 3
Func. diagram: 2198
Unit selection: -
Expert list: 1
Factory setting
[0] 0
[1] 2000
315