2 Parameters
2.2 List of parameters
Value:
0:
1:
2:
3:
Notice:
This parameter must always be set to the same value on both CUDs!
Note:
If value = 0:
There is no quasi-synchronization of the analog inputs on the two CUDs. Connector outputs r52030[0 to 6] on both
CUDs always indicate a value of 0%.
If value = 1:
The analog inputs of the right-hand CUD are interpolated on the left-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the left-hand CUD. Connector outputs r52030[0 to
6] on the right-hand CUD always indicate a value of 0%.
If value = 2:
The analog inputs of the left-hand CUD are interpolated on the right-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the right-hand CUD. Connector outputs r52030[0 to
6] on the left-hand CUD always indicate a value of 0%.
If value = 3:
The analog inputs of the right-hand CUD are interpolated on the left-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the left-hand CUD.
The analog inputs of the left-hand CUD are interpolated on the right-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the right-hand CUD.
p50709

CUD analog input 0 simulation selection / CUD AI 0 sim sel

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to select the simulation of analog input 0 (X177.25/26) on the CUD.
Value:
0:
1:
Dependency:
Refer to: p50707
Note:
The setpoint for the simulation is set in p50707.
p50710

CUD analog input 1 type / CUD AI 1 type

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the type for analog input 1 (X177.27/28) on the CUD.
Value:
0:
1:
2:
Note:
AI: Analog Input
p50711[0...n]

CUD analog input 1 scaling / CUD AI 1 scal

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-1000.0 [%]
Description:
Sets the scaling for analog input 1 (X177.27/28) on the CUD.
502
No synchronized analog inputs
6 synchronized analog inputs on left-hand CUD
6 synchronized analog inputs on right-hand CUD
6 synchronized analog inputs on left-hand and right-hand CUD
Simulation deactivated
Simulation activated
Bipolar voltage input (-10 V ... +10 V)
Bipolar current input (-20 mA to +20 mA)
Unipolar current input monitored (+4 mA to +20 mA)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
1000.0 [%]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 2075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2080
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2080
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]