p0819[0...2]

Copy Drive Data Set DDS / Copy DDS

DC_CTRL,
Can be changed: C2(15)
DC_CTRL_R,
Data type: Unsigned8
DC_CTRL_R_S,
P-Group: Data sets
DC_CTRL_S
Not for motor type: -
Min
0
Description:
Copies one Drive Data Set (DDS) into another.
Index:
[0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Note:
Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
p0820[0...n]

BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0

DC_CTRL,
Can be changed: C2(15), T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Data sets
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0821[0...n]

BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1

DC_CTRL,
Can be changed: C2(15), T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Data sets
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r0835.2

CO/BO: Data set changeover status word / DDS_ZSW

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned16
DC_CTRL_R_S,
P-Group: Displays, signals
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Displays the status word for the drive data set changeover.
Bit field:
Bit
02
Note:
Re bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Signal name
Internal parameter calculation active
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
31
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8565, 8570
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8565, 8570
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8575
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
FP
-
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents