2 Parameters
2.2 List of parameters
p50566
Speed controller optimization frequency response plot amplitude / f_plot amplitude
DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.01 [%]
Description:
Sets the amplitude for the frequency response plot for the optimization run "Speed control optimization for drives that
are capable of oscillation" (p50051 = 29).
p50567
Speed controller optimization frequency response plot time / f_plot time
DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.30 [s]
Description:
Sets the time for the frequency response plot for the optimization run "Speed control optimization for drives that are
capable of oscillation" (p50051 = 29).
In this case, an average is generated over the time set here per measuring frequency.
Note:
High values improve the result, however they slow down the measuring time.
For the 3.0 s setting, it takes approximately 9 minutes to plot the frequency response.
p50570[0...n]
Adaptation armature current controller changeover input / Adapt Ia chgov inp
DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the input quantity for armature current controller adaptation.
Value:
0:
1:
Dependency:
Refer to: p50571, p50572
p50571[0...n]
Adaptation armature current controller non-linear L activation / Adapt N_lin L act
DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to activate the adaptation of non-linear inductances for the armature current controller.
Value:
0:
1:
Dependency:
Refer to: p50570, p50572, r52350
478
Ia_act r52117
Ia_set r52119
Adaptation non-linear L active
Fixed value 100 % effective
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
5.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3.00 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 2660
Unit selection: -
Expert list: 1
Factory setting
1.00 [%]
Access level: 2
Func. diagram: 2660
Unit selection: -
Expert list: 1
Factory setting
1.00 [s]
Access level: 2
Func. diagram: 6853
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 6853
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS DCM