2 Parameters
2.2 List of parameters
Note:
Telegram monitoring is activated in the following cases:
- From receipt of the first error-free telegram
- After switching on of the electronics power supply
- From receipt of the first error-free telegram after telegram monitoring has responded (i.e. telegram monitoring
timeout).
The telegram monitoring time (p50797) depends on the baud rate set (p50793) The following minimum setting values
are recommended for safe operation:
- 300 baud --> p50797 = 0.520 s (recommended minimum value)
- 600 baud --> p50797 = 0.260 s (recommended minimum value)
- 1200 baud --> p50797 = 0.140 s (recommended minimum value)
- 2400 baud --> p50797 = 0.080 s (recommended minimum value)
- 4800 baud --> p50797 = 0.040 s (recommended minimum value)
If the "Automatic restart" function (p50086b > 0) has been selected on the peer-to-peer communication partner, only
a parameter setting p50797 > p50086 (on the communication partner) will be meaningful.
p50798

BI: P2P IF signal source for triggering F60012 / P2P F60012 sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for triggering fault F60012 "Telegram monitoring timeout".
Dependency:
Refer to: F60012
r50799[0...8]

P2P/CCP diagnostics / P2P/CCP diag

DC_CTRL
Can be changed: -
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the diagnostic information for the peer-to-peer interface and the interface to SIMOREG CCP.
Index:
[0] = Number of error-free telegrams
[1] = Number of erroneous telegrams
[2] = Number of byte frame errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of STX errors
[6] = Number of block check errors
[7] = Number of break errors
[8] = Number of timeout errors
Note:
The fault frequency is recorded with free-running counters; when a counter reaches 65535 it is reset to 0.
The diagnostic information in indexes 5, 6 and 8 is irrelevant for communication with SIMOREG CCP (p50790 = 6).
Possible causes for STX errors:
- Non-observance of start interval before STX
- STX incorrect, i.e. not equal to 02
Possible causes for timeout errors:
- Telegram monitoring timeout (p50797)
520
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 9300
Unit selection: -
Expert list: 1
Factory setting
53300.0
Access level: 1
Func. diagram: 6970, 9300
Unit selection: -
Expert list: 1
Factory setting
-