Bi: Cud Digital Input/Output 4 Signal Source / Cud Di/Do 4 Sig S; Bi: Cud Digital Input/Output 5 Signal Source / Cud Di/Do 5 Sig S; Bi: Cud Digital Input/Output 6 Signal Source / Cud Di/Do 6 Sig S; Bi: Cud Digital Input/Output 7 Signal Source / Cud Di/Do 7 Sig S - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Value:
0:
1:
Index:
[0] = DI/DO 4 (X177.15)
[1] = DI/DO 5 (X177.16)
[2] = DI/DO 6 (X177.17)
[3] = DI/DO 7 (X177.18)
Dependency:
The terminal must be set as an output (p50789[0...3]).
Refer to: p50789
Note:
DI/DO: Bidirectional Digital Input/Output
p50781

BI: CUD digital input/output 4 signal source / CUD DI/DO 4 sig s

DC_CTRL
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for digital input/output 4 (X177.15) on the CUD.
Dependency:
The terminal must be set as an output (p50789[0] = 1).
Refer to: p50789
p50782

BI: CUD digital input/output 5 signal source / CUD DI/DO 5 sig s

DC_CTRL
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for digital input/output 5 (X177.16) on the CUD.
Dependency:
The terminal must be set as an output (p50789[1] = 1).
Refer to: p50789
p50783

BI: CUD digital input/output 6 signal source / CUD DI/DO 6 sig s

DC_CTRL
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for digital input/output 6 (X177.17) on the CUD.
Dependency:
The terminal must be set as an output (p50789[2] = 1).
Refer to: p50789
p50784

BI: CUD digital input/output 7 signal source / CUD DI/DO 7 sig s

DC_CTRL
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for digital input/output 7 (X177.18) on the CUD.
Dependency:
The terminal must be set as an output (p50789[3] = 1).
Refer to: p50789
516
Not inverted
Inverted
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 2060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2065
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2065
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading