Co: Tm31 Temperature Actual Value / Tm31 Temp_Act Val; Tm150 Terminal Block Measuring Method / Tm150 Meas Method - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following applies:
- below the nominal response temperature, r4105[0...11] = -50 °C.
- above the nominal response temperature, r4105[0...11] = 250 °C.
For sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- the displayed value corresponds to the temperature actual value.
Refer to: p4100, p4111, r4112, r4113, r4114
Note:
r4105[0...11] = -300 °C is displayed in the following cases:
- temperature actual value invalid (F35920 ... F35931 output).
- no sensor selected (p4100[0...11] = 0).
The temperature actual values can be grouped using p4111[0...2] and the maximum value, minimum value as well as
the average value for each group evaluated (r4112[0...2], r4113[0...2], r4114[0...2]).
r4105

CO: TM31 temperature actual value / TM31 temp_act val

TM31
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [°C]
Description:
Displays the temperature actual value for the Terminal Module 31 (TM31)
Dependency:
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
- below the nominal response temperature, r4105 = -50°C.
- above the nominal response temperature, r4105 = 250 °C.
For sensor type "KTY84" (p4100 = 2), the following applies:
- the displayed value corresponds to the temperature actual value.
Refer to: p4100
Note:
r4105 = -300 °C is displayed in the following cases:
- temperature actual value invalid (F35920 output).
- no sensor selected (p4100 = 0).
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
p4108[0...5]

TM150 terminal block measuring method / TM150 meas method

TM150
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the measuring method for the terminal block X531 ... X536 for the Terminal Module 150 (TM150).
Re p4108[0...5] = 0 (1x2 wire evaluation):
- the temperature sensor is connected at terminals 1(+) and 2(-).
Re p4108[0...5] = 1 (2x2 wire evaluation):
- The first temperature sensor is connected at terminals 1(+) and 2(-).
- The second temperature sensor is connected at terminals 3(+) and 4(-).
Re p4108[0...5] = 2 (3 wire evaluation):
- the temperature sensor is connected at terminals 3(+) and 4(-).
- the measuring conductor is connected at terminal 1(+).
- terminals 2(-) and 4(-) must be jumpered.
Re p4108[0...5] = 3 (4 wire evaluation):
- the temperature sensor is connected at terminals 3(+) and 4(-).
- the measuring conductor is connected at terminals 1(+) and 2(-).
244
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2006
Max
- [°C]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 9549, 9576
Unit selection: -
Expert list: 1
Factory setting
- [°C]
Access level: 1
Func. diagram: 9625, 9626,
9627
Unit selection: -
Expert list: 1
Factory setting
1